NY DPS
Regulatory History

REV, Part 5: Counting Value — The Societal Cost Test Wins (January 2016)

New York chose the Societal Cost Test, rejected generic adders, and wrote location-specific distribution value into its benefit-cost rules.

Charlie Umberger5 min read

Part 5 of 11 in the Reforming the Energy Vision series (NY PSC Case 14-M-0101).

On January 21, 2016, the Commission issued its Order Establishing the Benefit Cost Analysis (BCA) Framework. It settled which test New York would use to decide whether distributed energy resources (DER) are worth buying, which benefits count, and how to value avoided distribution. Two weeks earlier, a demonstration plan from AVANGRID had made a point the framework would have to live with: DER can also add costs to the grid.

Which test?

The Joint Utilities wanted a narrower lens. They proposed "as the primary test a Distributer Cost Test (DCT)" in which "the impacts on wholesale commodity costs are excluded from the DCT, which focuses on delivery costs" [F1 p.14]. Large-customer and consumer groups AARP and Multiple Intervenors favored the Ratepayer Impact Measure (RIM), while other parties said the RIM "recognizes utility lost revenues, which are a sunk cost" [F1 p.15].

The Commission chose the broadest test, the Societal Cost Test (SCT). "The Commission adopts SCT as the primary measure of cost effectiveness under the BCA Framework. The SCT recognizes the impacts of a DER or other measure on society as a whole, which is the proper valuation." The Utility Cost Test (UCT) and RIM would "serve in a subsidiary role" [F1 p.15]. "The DCT test JU proposes is rejected as overly narrow" [F1 p.16].

It also made bill impacts the backstop rather than the gate: "A measure might reduce customer bills, leaving them better off, even if the UCT and RIM tests are not satisfied" [F1 p.16].

Which benefits?

The utilities would recognize operational benefits "only if they can be properly quantified and it is demonstrated that the costs are actually avoidable and material" [F1 p.22]. Advocates wanted more, including a generalized adder: "AEEI proposes that an adder of 10%" [F1 p.23].

The Commission drew a line on non-energy benefits (NEBs). "No commentator has been able to value any of the proposed societal NEBs with sufficient specificity to include them in the BCA Framework at this time." Nor would it adopt a generalized adder, since "Such an adder would increase the price of electricity without necessarily resulting in value to ratepayers" [F1 p.25].

On wholesale price suppression, the utilities argued the impacts "are mostly ephemeral" [F1 pp.26–27]. The Commission agreed they don't belong in the primary test: "Any price suppression over and above those market adjustments is essentially a transfer payment -- simply a shift of monetary gains and losses from one group of economic constituents to another." Price effects, it said, "are properly reflected in bill impact calculations" [F1 p.27].

How to value avoided distribution

Appendix C, the framework itself, carried Staff's 2015 language into the rule:

"Traditionally, avoided transmission and distribution (T&D) infrastructure need is considered on a system average basis and is estimated as a single dollar-per-kW value. However this estimation may significantly over- or under-value load modifications. Detailed marginal cost of service studies are necessary to fully determine the value of incremental or avoided T&D infrastructure needs. Utilities shall include the most up-to-date version of detailed marginal cost of service studies in their DSIP filings." [F1 p.91]

It kept the location test: a reduction near design limits "may allow the utility to defer needed investment whereas a similar load reduction in an area of greater excess capacity may have no impact on T&D costs" [F1 p.92]. It kept the overlap warning on transmission value already in capacity and energy prices [F1 p.89].

And it worked an example that shows how much timing matters. "A 1 MW battery with a 5-year service life is attached to an area substation in the Con Edison service territory." It discharges from 6 to 8 pm, "whereas the system peak generally occurs at 4 pm." So it does "reduce demand during the peak hours experienced by the area substation, but not those of the system as a whole," and it only gets credit for the area substation and sub-transmission costs it actually relieves. At marginal costs of $43.88/kW in 2015 and $82.90/kW in 2016, the five-year net present value came to $358,205 [F1 pp.92–93].

The other side of the ledger: DER can create costs too

On January 8, AVANGRID's NYSEG and RG&E filed the implementation plan for their Flexible Interconnect Capacity Solution demonstration. It described a problem that runs opposite to deferral. "The traditional interconnection process assumes that a utility must invest in network facilities (network reinforcements) necessary to accommodate the maximum rated capacity of proposed DERs or otherwise limit the capacity that can be interconnected." The developer pays, "and as a result the DER opportunity may not be economical" [F2 p.4].

AVANGRID's view was that "The traditional reinforcement model has met system requirements to date, but may no longer be efficient under a REV environment that contemplates a significant expansion of DER capacity." Its alternative: during constrained periods, the developer accepts curtailment "in return for reducing or avoiding incremental network reinforcement costs" [F2 p.4]. The driver was volume: "the high volume of current interconnection applications for large-scale distributed solar photovoltaic (PV) projects" in NYSEG and RG&E territory [F2 p.6].

The takeaway

By January 2016 New York had a test (the SCT), a rule for distribution value (granular, location-specific, based on marginal cost studies), and a worked example showing that the same battery is worth different amounts depending on whose peak it hits. It also had an early signal that adding DER could raise grid costs as well as lower them. The utilities' marginal cost studies, due with their distribution plans, would now carry a lot of weight.


Sources

F# Filing Date Document Pages cited Links
F1 14-M-0101, item 680 2016-01-21 Order Establishing the Benefit Cost Analysis Framework (with Appendix C) p.14, p.15, p.16, p.22, p.23, p.25, pp.26–27, p.27, p.89, p.91, pp.92–93, p.92 View filing · Original (NY DPS)
F2 14-M-0101, item 663 2016-01-08 AVANGRID Flexible Interconnect Capacity Solution demonstration implementation plan p.4, p.6 View filing · Original (NY DPS)

Page numbers are physical PDF pages; the order's own page numbers are 3 lower, and Appendix C restarts its own numbering.

Case 14-M-0101

Follow the case
About the Author

I have spent the last decade trying to get distributed energy resources on the grid, paid, operated, and integrated into utility operations and business.

Related Insights

Regulatory History

REV, Part 4: The "Value of D" — Staff's 2015 White Papers and the Utilities' Reply (July–October 2015)

In the summer of 2015, Staff issued two white papers: one on benefit-cost analysis (July 1) and one on ratemaking and utility business models for Track Two (July 28). Together they set out New York's first detailed answer to the question every DER docket asks: what is a…

Regulatory History

REV, Part 6: Planning for Growth — Baldwinsville and the DSIP Guidance (March–April 2016)

By spring 2016, New York had a test for value. What it needed next was information: where the grid was constrained, where load was growing, and where DER could actually defer something. Two filings from March and April show the gap from both ends: one utility's first open…

Compensation & Rates

Fast Forward: New York Is Still Arguing Over What a Kilowatt Avoids

The rest of this series moves through Case 14-M-0101 one filing at a time and never looks ahead. This post breaks that rule on purpose. Before we go back to 2014, here's where two of REV's biggest value questions stand in late 2026.